UL90 REQUIREMENTS
FOR PRE-ENGINEERED METAL BUILDINGS
FIXED SYSTEM CONSTRUCTION #205
1. Metal panels - 24 gauge or
heavier, 24", 18", or 12" wide panels continuous over two or more
spans
2. Panel clips - fixed (high, low, utility)
3. Fasteners - two per clip.
4. Purlin - minimum 16 gauge, minimum yield strength 55 KSI, maximum
spacing 5'-0" on center.
5. Optional accessories - insulation (maximum thickness 6"), thermal
spacer (for use with high systems).
FLOATING SYSTEM CONSTRICTION #205A
1. Metal panels - 24 gauge or
heavier, 24", 18", or 12" wide panels continuous over two or more
spans
2. Panel clips - fixed (high or low)
3. Fasteners - one per clip except when optional skylights are used.
4. Purlin - minimum 16 gauge, minimum yield strength 55 KSI, maximum
spacing 5'-0" on center.
5. Optional accessories - insulation (maximum thickness 6"), thermal
spacer (for use with high systems), skylights (insulated or uninsulated) with
stiffener plate.
C A U T I O N
For UL 90 rated roofs, these requirements must be followed. If you have any questions, please call Dean Steel Buildings, Inc., before proceeding.
·
Diaphragm capabilities and purlin stability are not provided by Deans
ProSeam roof system. Therefore, other bracing may be required to
conform to A.I.S.C. or A.I.S.I. specifications.
IMPORTANT
|
It will greatly facilitate designing, quoting, ordering, and/or erecting the Dean Pro Seam roof if you determine which system you need or have, based on the building width and insulation requirements. |
||
|
FIXED |
FLOATING |
|
|
BUILDING
WIDTH |
BUILDING
WIDTH
|
|
|
LOW FIXED |
LOW FLOATING |
|
|
HIGH FIXED |
HIGH FLOATING |
|
|
NOTE: |
||
|
1. The above applies to pre-engineered metal buildings. |
||
|
2. Bar joist construction (all widths) requires a floating system. |
||
|
3. As with all standing seam roof systems, a sound insulator (e.g. blanket insulation) is |
||
|
required between the panel and
substructure. |
||
|
Thermal Spacer Selection Chart |
||
|
For use over blanket insulation installed over purlins or joists |
||
|
|
Low System |
High System |
|
No Insulation |
3/8 Thermal Spacer |
N/A |
|
3 Insulation |
3/8 Thermal Spacer* |
1 Thermal Spacer |
|
4 Insulation |
N/A |
5/8 Thermal Spacer |
|
6 Insulation |
N/A |
3/8 Thermal Spacer |
|
*May cause bulge at purlins. Do not use if aesthetics are a concern. |
||
![]() |
CAUTION Never Use a Hammer to force the panels to snap together. This will cause severe damage to the panel and will nullify any warranties. |